APC Back-UPS Pro BR1200SI
P/N: BR1200SI კოდი: 48729დამატებითი ინფორმაცია
| წონა | 11.7 კგ |
|---|---|
| ზომები | 26 × 10 × 36.8 სმ |
| მწარმოებელი | APC |
| UPS-ის ტიპი (Topology) | Line interactive |
| UPS-ის ფორმ ფაქტორი | Tower |
| UPS-ის სიმძლავრე | 1.2kVA |
| UPS-ის სიმძლავრე (Input:Output phase) | 1:1 ფაზა |
| Power, W | 720 |
| Signal type when running on battery | Sine wave |
| Height, units | No |
| Rack mounting ears included | No |
| Rack Mount Rails Included | No |
| Possible wall mount | No |
| Rated input voltage, V | 220-240 |
| Input voltage range, V | 176-294 |
| Input frequency range, Hz | 50/60 ±3 |
| Rated output voltage, V | 230 |
| Output voltage range, V | 230 |
| Output frequency range, Hz | 50/60 ±1 |
| Type of power output connectors | IEC 60320 C13 |
| Number of power output connectors | 8 |
| Availability of groups of controlled connectors | No |
| Number of groups of controlled connectors | No |
| Battery type | Lead Acid |
| Nominal battery capacity, Vah | 216 |
| Built-in battery voltage, V | 12 |
| Capacity of the built-in battery, Ah | 9 |
| Number of built-in batteries, pcs. | 2 |
| Battery recharge time up to 90%, hours | 16 |
| Autonomous operation time at 50% load, min | 14 |
| Autonomous operation time at 75% load, min | 7.5 |
| Autonomous operation time at 100% load | 4.5 |
| Replaceable battery cartridge | APCRBC161 |
| User replacement of batteries | Yes |
| Possible connecting additional batteries | No |
| Article number of the additional external battery | No |
| Max. number of additional batteries | No |
| Sound indicators | Yes |
| LED indicators | Yes |
| Display (monitoring) | Yes |
| Display (UPS setup and monitoring) | No |
| Data line protection | Yes |
| Poss. connection to PC via RS-232 | No |
| USB type-A interface for charging mobile electronics | Yes |
| USB type-C interface for charging mobile electronics | Yes |
| Smart-Slot for connecting expansion cards (SNMP,...) | No |
| Part number of a suitable network card | No |
| Network card included | No |
| Temperature sensor included | No |
| Battery self-diagnosis | Yes |
| Cold start | Yes |
| Hot-swappable batteries | No |
| Dry contacts (Emergency Power Off function) | No |
| Ability to operate in N+1 redundancy mode | No |
| Switching time, ms | 8-10 |
| Noise level, dB | 45 |
| Pulse energy absorption, J | 509 |
| Mains power cable (included) | No |
| UPS warranty, years | 2 |
| Battery warranty, years | 2 |